New version of the catalogue Mass ventilation of garages!
In the catalogue we present suitable fan types and possible ventilation methods for specific garage buildings.
The design method using Computational Fluid Dynamics (CFD) simulation software is commented on.
The catalogue can be downloaded here.

NEO-V smoke and heat extraction dampers

Square dampers for heat and smoke extraction from the fire affected section.
Read more
price on request
Availability: on request [27.4.2024, 00:00] Update
Goods cannot be ordered online.
Contact our sales specialists
or visit our branches.

Product code:
Product description
Description

The NEO-V smoke dampers are designed for heat and smoke extraction systems from the fire affected section. The dampers are certified according to EN 12 101-8 and tested according to EN 1366-10. Classification is made according to EN 13501-3+A1:2010.

Use

The NEO-V dampers can be installed in systems for the extraction of heat and smoke from multiple fire compartments (multi). They can be installed in both HVAC systems and in combination with a conventional HVAC system. They are designed for systems with automatic activation. Installation of dampers is allowed in a pipe that passes through a ceiling or wall, or directly into a ceiling or wall (the pipe route may start with this element). The fire resistance of the dampers is EI 120 (vew how i<->o) S 1500 Pa C10000 AA multi. The tightness of the casing corresponds to class C and the damper blade to class 4. Testing has been carried out in accordance with EN 1751:2002.

Mounting

The NEO-V fire dampers are designed for square ducts from 100 × 200 mm to 1200 × 900 mm or 900 × 1200 mm (W × H). The damper is designed with an emphasis on minimum pressure drop and is suitable for installation in all common building structures. The damper can be installed with the mounting axis in both vertical and horizontal positions.

Information

The damper consists of:
- a square casing made of galvanized steel sheet, alternatively stainless or acid resistant steel
- a movable damper blade made of fire resistant material
- smoke and fire seals
- a control mechanism, alternatively an EMS module for remote control of the damper function