Information
- it has a galvanized sheet metal cabinet, the cabinet includes a terminal block and internal plumbing
- the heating rods are stainless steel
- it is equipped with two capillary thermostats, one is working (60 ˚C), the second one is safety (safety thermostat switches off at 120 ˚C)
- the reset button of the safety thermostat is located on the cabinet, during installation it is necessary to position the heater with regard to the inspection activity
- the minimum air velocity in the heater is 2 m/s
- the continuous regulation is carried out by the TTC 2000 regulator, TTC 40
- the protection is IP43
- they are mounted behind the fan in the direction of the air flow, between the fan and the heater it is necessary to insert about 1 m of pipe
- standard connection to the square pipe, the dimensions of the connection are identical to the fans IRB, IRT
- suitable for DIRECT AIR assembled units
- apart from the standard range of outputs the following versions are available:
IBE-200 - 6 kW
IBE-225 - 11,1 kW
IBE-250 - 11,1 kW
IBE-285 - 16,5/22,5 kW
IBE-315 - 15/22,5 kW
IBE-355 - 15/22,5 kW
IBE-400 - 16,6/33,2 kW
IBE-450 - 58,2/66,6 kW
Notice
When turning off the fans, the dampers in the system may not close until the bars have cooled down, otherwise there is a risk of damage to the heater and other equipment.