Cabinet
is made of durable high density EPP. The front metal panel and sides are powder coated white. Connection circular sockets Ø 125 mm are fitted on the sides of the enclosure. The necks are fitted with a double-edged seal. Revision access is from the front of the unit.
Fans
The unit contains two radial fans with rearward curved blades with EC motor.
Motors
They are single-phase EC with low power consumption, 230 V / 50 Hz. IP21 protection.
Recuperation
Counter-current heat exchanger with up to 93% efficiency. The heat exchanger is accessible by opening the front panel.
Filters
The unit is fitted with two G4 class (ISO coarse 65%) plate filters for both the intake and exhaust.
Outdoor filters
- AFR-NEMBUS 210 G4/G4 set
- AFR-NEMBUS 210 F7/G4 set
Electrical connections
The unit is designed for direct connection via mains plug. Power supply 230 V / 50 Hz.
Regulation
The unit is equipped with a fully automatic control system with flow regulation according to relative humidity without the need for any further intervention in the control of the unit. The unit is equipped with four combined temperature and relative humidity sensors. The performance characteristics for each speed are indicated in the performance characteristics. The designer wired controller allows for fan speed adjustment, manual by-pass control, BOOST function activation, automatic operation activation and filter clogging indication. Other unit settings are made using the DIP switches and potentiometers on the unit's control board when the front cover is removed. A weekly program can be set for the automatic mode. The frost protection system allows the unit to operate down to an outdoor temperature of -10 °C without the need for additional preheating or reheating. The NEMBUS 210 can be supplemented with NEMBUS-VOC and SABIK-NEMBUS-SF constant airflow modules. Connection to Connectair (cloud S&P) is possible.
Mounting
The unit is designed for horizontal ceiling mounting or vertical wall mounting indoors. The required ambient temperature is between 10 and 50 °C. The unit shall be mounted to provide sufficient space for removal of the unit face, replacement of filters, connection of the condensate drain to the SF-P 138 odour trap and for periodic inspection of the wiring. If the unit is mounted above the soffit, an inspection opening for the operator is required.
Accessories
- ED Flex® System circular ductwork
- AIRSENS-CO2 spatial CO2
- NEMBUS-PH integrated preheat
- NEMBUS-VOC integrated VOC sensor
- SONOULTRA flexible silencer
- SABIK-NEMBUS-SF module for constant air flow
Instructions
The unit is not equipped with its own heater as standard. If preheating is required, an integrable NEMBUS-PH module or external MBE and MBW duct heaters with corresponding control elements can be used. After basic set-up by the installer, the unit requires no further adjustment. Filter changes are recommended at least once a year. The design of the ventilation system and its use in buildings with category B gas appliances (gas boilers and open chamber water heaters) or open hearth appliances burning solid or liquid fuels with flue gas exhaust to the chimney is governed by the applicable regulations. Ventilation must comply with the building fire safety regulations.
Information
A complete ventilation system with a small unit designed for ventilation of flats, apartment buildings and family houses. The unit is designed for permanent operation.
Highlights
The NEMBUS 210 heat recovery unit is part of the New Green Savings Programme under the code SVT30864.