- capillary power regulator for water heaters MBW 100 to MBW 250
- consists of a control valve driven by a capillary sensor and a control knob
- regulation is continuous depending on the control deviation
- connection size is 3/4" or 3/8"
- water temperature up to +120 °C
- maximum shut-off pressure is 1 bar
- maximum operating pressure is 10 bar
- maximum flow rate is 300 l/hr
- temperature setting 7 °C - 28 °C
- control range and scale on the control knob is divided into 6 parts
- capillary length is 5 m
Highlights
For use in the treatment of perpetual air, it is necessary to provide independent blocking of the operation of the supply fan and inlet damper from the capillary frost protection (see supplementary illustration).
Setting the thermostat
- is carried out on the control knob
* - frost protection symbol, if the control knob is in this position, the thermostatic valve automatically opens when the water temperature drops below 6 °C
2 - water temperature approx. 12 °C
3 - water temperature approx. 16 °C
4 - water temperature approx. 20 °C
5 - water temperature approx. 24 °C
6 - water temperature approx. 28 °C