MBE-AFP 125/0,4 aktívna protimrazová ochrana

Active frost protection for reheating the fresh air supply.
Read more
B2B clients will see their prices after logging in
10 168,00 CZK excl. VAT
12 303,28 CZK incl. VAT
Availability: In stock [22.12.2024, 16:10] Update

Product code: ED510100020
Product description
Cabinet

- it is made of galvanized sheet metal without insulation as standard, on request it is possible to equip the cabinet with synthetic rubber insulation or EPP insulation
- the cabinet includes a terminal block and an electronic control unit with two temperature sensors
- designed for EHR 140, 280, 300, 325 and 480, DOMEO 210, IDEO 325 and 450 units
- the heating rods are made of stainless steel
- equipped with a safety grille at the inlet and outlet

El. connection

- 2 thermostats, operating thermostat 45 °C and safety thermostat 70 °C, safety fuse 110 °C non-reversible
- NTC temperature sensor to set the operating value according to the inlet temperature, adjustable by internal potentiometer 0-20 °C
- NTC temperature sensor to set the outlet temperature, adjustable by an internal potentiometer 0-30 °C
- safety thermostat button is accessible inside the terminal block, on request it can be placed on the cabinet lid
- the heater must be positioned to ensure free access for service and maintenance
- IP42 protection

Regulation

- the controller is powered directly from the mains 230 VAC / 50 Hz
- the output temperature is continuously controllable 0-100%, internally adjustable by potentiometer 0-30 °C
- the controller allows connection of an external channel sensor (electrical insulation class II.), which senses the current air temperature behind the heater or recuperator
- it is possible to block the heater when the input temperature reaches the set value of 0-20 °C
- it is possible to block the heater by connecting an external air flow sensor, pressure sensor, room thermostat, etc.

Accessories

- TGCU-3-IZ - external output for temperature sensor - electrical insulation class II.

Information

The MBE AFP heater can be used very simply to reheat the incoming fresh air. If setting the outlet temperature with the internal potentiometer is not sufficient, a room wall thermostat with an expansion contact can be used, which will block the heater operation when the room temperature is reached. If the room temperature drops, the thermostat will unlock the heater operation.

Warning

A minimum of 0.5 m of steel pipe must be installed in front of and behind the heater to prevent contact with combustible parts. The use of an air flow sensor or pressure sensor is required to block the operation of the heater if the flow rate or flow velocity falls below the permitted limit.

When shutting down the HVAC system, the fan must be allowed to run for a minimum of 2 min to cool the heating rods.
Otherwise, damage to the heater and other equipment may occur.

Full description
Downloads
Technical sheets, manuals and declarations
Datasheet .pdf (395.04 kB)
Operating Instructions .pdf (701.40 kB)
Contact Us