Information
- capillary power regulator for water heaters MBW 100 to MBW 250
- consists of a control valve driven by a capillary sensor and a control knob
- regulation is continuous depending on the control deviation
- water temperature up to +120 ˚C
- maximum shut-off pressure is 1 bar
- maximum operating pressure is 10 bar
- maximum flow rate is 300 l/hr
- temperature setting 7 ˚C-28 ˚C
- control range and scale on the control knob is divided into 6 parts
- capillary length is 5 m
Thermostat setting:
- is carried out on the control knob
* - if the control knob is in the frost protection position, the thermostatic valve opens automatically when the air temperature drops below 6 °C
2 - air temperature approx. 12 °C
3 - air temperature approx. 16 °C
4 - air temperature approx. 20 °C
5 - air temperature approx. 24 °C
6 - air temperature approx. 28 °C